Permit: T09CM00440

Parcel: 132081560


Addresses:

1979 E AJO WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00440

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/12/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) OK ABOVE CEILING-REPLACED FLEX
2) CONDUCTOR TAPE IDENTIFICATION TO ENCIRCLE CONDUCTORS
3) FINISH 1, 5, 6 & 9 FROM PREVIOUS INSPECTION
11/03/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
10/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS AND CEILINGS RESTRAINT
2) OK CEILINGS TRASH COMPACTOR
3) OK WALLS AND CEILINGS UPS ROOM
4) OK MAKE UP TO 9 LIGHT POLES-OK TO INSTALL
10/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALK IN COOLER WALLS
2) OK WALLS, EXCEPT AS NOTED
3) OK HARDLIDS, EXCEPT AS NOTED
4) PLUMBERS TAPE IS NOT AN APPROVED SUPPORT METHOD, ALSO THHN IS NOT AN APPROVED SUPPORT METHOD
5) PROTECT CONDUCTOR PER 356.42 AND 300.4
6) FINISH TOWER, TRASH ENCLOSURE AND PORCHES
10/06/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) TIGHTEN LOOSE FITTINGS
2) PROTECT VDV CABLING AT RACEWAY ENDS
3) SUPPORT PVC CONDUIT PER CODE
4) CANNOT USE SHEETMETAL THREAD SCREWS FOR GROUNDING
5) PROTECT PVC AT BASE PLATE
6) SUPPORT EMT ABOVE PANELS AND AS PER CODE
7) TOWERS NOT READY
10/01/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*