Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/09/2009 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 09/10/2009 | ELECTRIC - UFER | Partial Approval | 1. CANNOT RUN IN FOOTPRINT OF FITTING WITH CONDUIT. 2, BOND 4/0 TO REBAR 3. USE LISTED & APPROVED FITTINGS WITH PVC *NOTE SOME RUNS HAVE 360 ALREADY OK 4/0 AFTER CORRECTIONS OK PRIMARY FEEDS CONDUITS TO WITHIN 15' OF TEP OK POLE BASES AS MARKED #4 GROUND IS INEFFECTIVE AS A SUPPLEMENTAL ELECTRODE CONDUCTOR OK PVC UNDER SLAB OK TRACH ENCLOSER PVC |
|
| 09/09/2009 | ELECTRIC - UFER | Partial Approval | IVRS - Inspection :* |