Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T09CM00435
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/27/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1. OK FOR CEILING TILES 2. BE SURE CONDENSATE IS TERMINATED TO AN APPROVED LOCATION. |
|
05/26/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. METAL TAPE IS NOT INSULATION, PLEASE INSULATE ALL BRANCH TAPS 2. RETURN TAP IS FASTENED TO TRUSS WITH PANDUIT STRAP 3. REMOVE AND CAP ABANDONED DUCT OPEN TO ABOVE CEILING SPACE. |