Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00435

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/27/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1. OK FOR CEILING TILES
2. BE SURE CONDENSATE IS TERMINATED TO AN APPROVED LOCATION.
05/26/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. METAL TAPE IS NOT INSULATION, PLEASE INSULATE ALL BRANCH TAPS
2. RETURN TAP IS FASTENED TO TRUSS WITH PANDUIT STRAP
3. REMOVE AND CAP ABANDONED DUCT OPEN TO ABOVE CEILING SPACE.