Permit: T09CM00429

Parcel: 131070050


Addresses:

6142 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T09CM00429

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2009 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/27/2009 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CORRECT DRAINAGE FOR ADDITIONAL SINK IN KITCHEN OR DELETE
2. THERE IS A PLANT NURSERY ON THIS SITE, TUCSON WATER BACKFLOW WILL BE NOTIFIED FOR POSSIBLE NEED FOR BACKFLOW PROTECTION
05/21/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RED GUARD SHOWER LINE-OK
2) PIPING FOR LAV WATER CLOSET AND SHOWER-OK
05/07/2009 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
WATER TEST FOR REVISION FOR SHOWER DRAIN OK

1. THIS SHOWER WILL REQUIRE AN APPROVED LINER WITH TEST - PLEASE SEE NOTES #1 AND PROVIDE INFORMATION PROVING THAT THIS VALVE MEETS ASSE 1016 REQUIREMENTS FOR TEMP AND PRESSURE BALANCING PER 2006 UPC

PLEASE SEE NOTE #3 THIS SHEET AND PROVIDE TEST ON SHOWER RISER
04/28/2009 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
THIS INSPECTION FOR INTERMEDIATE PLUMBING
1. PROVIDE A TEMPERATURE AND PRESSURE BALANCING TUB AND SHOWER VALVE PER 2006 UPC
2. FLOOR PLAN SHOWS A TUB AND YOU HAVE INSTALLED IMPROPER DRAINAGE AND FITTINGS FOR A SHOWER
3. HAVE ALL NEW PIPING UNDER TEST
4. HAVE YOUR TUB INSTALLED CORRECTLY WITH TEST FOR DRAIN AND OVERFLOW
5. PROVIDE PROTECTION PLATES FOR PLUMBING PIPING