Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00429
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/25/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. HAVE RECEPTACLE WITH OPEN EQUIPMENT GROUND 2. HAVE RECEPTACLE WITH NO POWER 3. PROPERLY INSTALL WIRING UNDER SINK. SEAL OPEN KNOCKOUT 4. INSTALL DISCONNECTING MEANS FOR WATER HEATER NEC 422 5. PROVIDE DISCONNECTING MEANS FOR FLUORESCENT FIXTURES PER NEC 410.73(G) 6. INSTALL GFI SERVICE RECEPTACLE FOR ROOFTOP UNIT |
|
| 06/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* UNIT LOCKED -- NO ACCESS |
|
| 04/28/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |