Permit: T09CM00426

Parcel: 11304028C

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/15/2009 BUILDING - FINAL Approved
09/04/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ? WALL SCREWS ARE NOT FOR WOOD CONNECTORS
06/30/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL RECEPTACLES AT COOLER DISCONNECT
2) 5J ELECTRIC CABLE IS NOT ALLOWED FOR BRANCH CIRCUITS
3) WOOD IN CONTACT WITH EARTH MUST BE PROPERLY TREATED (ITEM 1 ABOVE)
4) PLEASE READ PREVIOUS CORRECTION LIST (2 ABOVE)
5) SCREEN REQUIRED FOR ATTIC VENTS (1/8"-1/4" MESH)
6) FRONT GABLE VENT REQUIRED
7) FINISH SHEETROCK
8) YOU MAY NOT HAVE THE KRAFT PAPER ON INSULATION EXPOSED IN A CONCEALED SPACE
06/17/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REPAIR COOLER STAND (MAKE STRUCTURALLY SOUND)
2. SUPPORT WATER SUPPLY TO COOLER PER UPC
3. PROVIDE CORRECT DISCONNECTS/FUSING/WIRING TYPE FOR COOLER
4. REPLACE GABLE END VENTS; INSULATION FOR CEILINGS CEILINGS COVERINGS
5. BEDROOM WINDOWS MUST BE OPERABLE
6. TPRV DISCHARGE LINE REQUIRED ON WATER HEATER
7. LABEL DISCONNECTS @ SUB-PANEL