Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T09CM00423
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/18/2009 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* A WOOD SHIM IS NOT AN APPROVED SUPPORT AFTER INSTALLING LISTED SUPPORT, OK TO COVER FLOOR & WALLS |
|
03/16/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU HAVE A COUPLING W/IMPROPER ALIGNMENT THAT IS CREATING A SHORT SECTION W/BACK PITCH |
|
03/13/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE MIN. 1/4" PER FOOT SLOPE, CORRECT BACKPITCH AT COUPLING. RETEST. OK TO COVER FRONT SIDE OF WALL ONLY IF BACKSLIDE IS ACCESSIBLE USE APPROVED TRANSITION COUPLING AT REVENT. |
|
03/11/2009 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOU MAY NOT DUMP A WASTE LINE INTO A VENT |