Permit: T09CM00418

Parcel: 122160020


Addresses:

3530 E GRANT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00418

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) OK FOR CEILING TILES
3) PLEASE VERIFY PERMITS AND INSPECTION FOR NEW A/C UNITS ON 3510 AND 3514 E. GRANT RD
04/06/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CORRECTIONS HAVE NOT BEEN MADE
04/03/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSULATE WYE BRANCH FITTINGS ABOVE CEILING
2. TIE WRAPS NOT APPROVED AS DUCT SUPPORT
3. SUPPORT FLEX DUCT OFF OF GRID
4. INSTALL EXHAUST SYSTEM