Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/30/2009 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXIT AND LIGHTING NOT ON PROPER CIRCUIT 2. CHANGE CIRCUIT TO MATCH PRINT OR GET LETTER FROM ARCHITECT |
|
| 04/09/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. 1 BOX IN FRONT NEEDS TO BE MOUNTED OR BRACED 2. 1 BOX IN FIRST OFFICE NEEDST OBE MOUNTED OR BRACED |