Permit: T09CM00398

Parcel: 14043011A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00398

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/19/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/18/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE SPIN IN BRANCH TAPS PER PLANS DOVE TAIL NOT ACCEPTABLE
2. PROVIDE VOLUME DAMPERS IN RETURN DUCTS PER PLANS
3. ROUND DUCT TO BE SUPPORTED FROM STRUCTURE PER PLANS (NOT RESTING ON WALL)
4. PROVIDE DUCT SUPPORT WITHIN 24" OF BRANCH TAPS AND/OR ELBOWS, SUPPORTS NOT TO EXCEED 10'