Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/15/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DERATE CONDUCTORS PER 310.15 2. SUPPORT 2 1/2" CONDUITS AT SUB-PANEL 3. FILL UNUSED OPENINGS IN BOXES 4. WORK NOT AS PER PLANS -- PLEASE REVISE OR INSTALL AS PER PLANS 5. RECEPTACLE COVERS TO BE AS PER 406.8 6. NEED REJECTION PINS 7. LABEL DISCONNECT |