Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00388
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/15/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DERATE CONDUCTORS PER 310.15 2. SUPPORT 2 1/2" CONDUITS AT SUB-PANEL 3. FILL UNUSED OPENINGS IN BOXES 4. WORK NOT AS PER PLANS -- PLEASE REVISE OR INSTALL AS PER PLANS 5. RECEPTACLE COVERS TO BE AS PER 406.8 6. NEED REJECTION PINS 7. LABEL DISCONNECT |