Permit: T09CM00376

Parcel: 136382140


Addresses:

4640 S GOLDENROD PL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
03/26/2009 BUILDING - FINAL Approved IVRS - Inspection :*
03/16/2009 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUB-PANEL FOR ADDITION IS DBL LUGGED AT MAIN PANEL
2) ALL CIRCUITS IN SUB-PANEL CAN BE FED BY 1-20 AMP CIRCUIT FROM MAIN PANEL, ELIMINATING NEED FOR SUB-PANEL
3) CHECK FOR OPEN GROUNDS IN ADDITION
4) USE PROTECTIVE GROMMETS OR ROMEX CONNECTORS WHERE WIRES ENTER HOUSE FROM PANEL
5) GUT SUB-PANEL AND USE AS JUNCTION PANEL. SCREW COVER SHIRT