Permit: T09CM00366

Parcel: 13015001A


Addresses:

4646 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T09CM00366

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
04/30/2009 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/31/2009 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WATER TEST UNDERGROUND TO POINT OF CONNECTION TO EXISTING VENT WITH ADDITION OF FLOOR DRAINS WITH TRAP PRIMERS OK PENDING REDLINE OF THIS ON APPROVED DRAWINGS ON SITE. PIPE WRAPS OK.
03/27/2009 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE FULL SIZE 4" C/O FOR THIS BRANCH
2. TO WET VENT THE URINAL YOUR WET VENTED SECTION IS REQUIRED TO BE 2 PIPE SIZES LARGER THAN THE REQUIRED FIXTURE DRAIN
3. HOW WILL YOU MAKE YOUR URINAL CONNECTION WITH YOUR FITTING THAT CLOSE TO THE FINISHED WALL?
4. PER 2006 UPC YOU ARE REQUIRED TO HAVE FLOOR DRAINS IN THE RESTROOMS