Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T09CM00366
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/30/2009 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
03/31/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST UNDERGROUND TO POINT OF CONNECTION TO EXISTING VENT WITH ADDITION OF FLOOR DRAINS WITH TRAP PRIMERS OK PENDING REDLINE OF THIS ON APPROVED DRAWINGS ON SITE. PIPE WRAPS OK. |
|
03/27/2009 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE FULL SIZE 4" C/O FOR THIS BRANCH 2. TO WET VENT THE URINAL YOUR WET VENTED SECTION IS REQUIRED TO BE 2 PIPE SIZES LARGER THAN THE REQUIRED FIXTURE DRAIN 3. HOW WILL YOU MAKE YOUR URINAL CONNECTION WITH YOUR FITTING THAT CLOSE TO THE FINISHED WALL? 4. PER 2006 UPC YOU ARE REQUIRED TO HAVE FLOOR DRAINS IN THE RESTROOMS |