Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES FOR FINAL PROVIDE THE OBD DAMPERS IN SUPPLY DIFFUSERS OR PROVIDE A LETTER FROM THE ENGINEER TO DELETE |
|
| 08/18/2009 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL FLEX DUCTS AND VAPOR BARRIERS AS PER PLANS |