Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T09CM00363
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2009 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* 1) WEST WALL-TOPPED OUT; EMBEDS ARE IN PLACE-OK TO GROUT |
|
07/02/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) WEST WALL TOPPED OUT AT 15'; ENTRY WALLS AT 8'-8" TO 12'-8" (ABOVE LINTEL) EMBEDS TO BE ADDED TO WEST WALL 7/6/09 |
|
07/01/2009 | REINFORCED MASONRY PRE-GROUT | Not ready for Inspection | IVRS - Inspection :* 1) CONTRACTOR CANCELLED-WILL RECALL |
|
06/30/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) EAST WALL TOPPED OUT AT 15', NORTH WALL AT 14'-3", WEST WALL AT 12'-4" OK TO GROUT PROGRESS AREAS |
|
06/26/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) BOND BEAM FOR LEDGER ANGLE OK S4 205 2) PROVIDE SPECIAL INSPECTION 3) EAST WALL TO 14'-4" |
|
06/24/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* POCKETS FOR STEEL BEAMS AT MASONRY WALL CUT AS PER DETAILS #203 (EAST & WEST) - MASONRY WALL @ 12'8" |
|
06/23/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* EAST WALL @ 8'8"-12'8" - EMBEDS TO BE SET PER PLANS EXISTING BLDG. @ SOUTH - ROOF LINE TO BE CUT EAST WALL TO BE EXTENDED - DETAIL #203 |
|
06/22/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WEST AND NORTH WALLS @ 8'4" -- OK TO GROUT *ENSURE NOTE #12 IS FOLLOWED FOR SOLID GROUTING |
|
06/17/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WEST WALL @ 8'4"; SW ENTRY AREA @ 4'8"; EAST WALL @ 8'4" -- OK TO GROUT PROGRESS AREAS |
|
06/16/2009 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* PERIMETER WALLS @ 0"-52" @ 8 X 8 X 4 CMU'S - OK TO GROUT 1ST LIFT |