Permit: T09CM00363

Parcel: 12701001B


Addresses:

421 N ARCADIA AV

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/06/2009 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
1) WEST WALL-TOPPED OUT; EMBEDS ARE IN PLACE-OK TO GROUT
07/02/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) WEST WALL TOPPED OUT AT 15'; ENTRY WALLS AT 8'-8" TO 12'-8" (ABOVE LINTEL) EMBEDS TO BE ADDED TO WEST WALL 7/6/09
07/01/2009 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1) CONTRACTOR CANCELLED-WILL RECALL
06/30/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) EAST WALL TOPPED OUT AT 15', NORTH WALL AT 14'-3", WEST WALL AT 12'-4" OK TO GROUT PROGRESS AREAS
06/26/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) BOND BEAM FOR LEDGER ANGLE OK S4 205
2) PROVIDE SPECIAL INSPECTION
3) EAST WALL TO 14'-4"
06/24/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
POCKETS FOR STEEL BEAMS AT MASONRY WALL CUT AS PER DETAILS #203 (EAST & WEST) - MASONRY WALL @ 12'8"
06/23/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
EAST WALL @ 8'8"-12'8" - EMBEDS TO BE SET PER PLANS
EXISTING BLDG. @ SOUTH - ROOF LINE TO BE CUT
EAST WALL TO BE EXTENDED - DETAIL #203
06/22/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST AND NORTH WALLS @ 8'4" -- OK TO GROUT
*ENSURE NOTE #12 IS FOLLOWED FOR SOLID GROUTING
06/17/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WEST WALL @ 8'4"; SW ENTRY AREA @ 4'8";
EAST WALL @ 8'4" -- OK TO GROUT PROGRESS AREAS
06/16/2009 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
PERIMETER WALLS @ 0"-52" @ 8 X 8 X 4 CMU'S -
OK TO GROUT 1ST LIFT