Permit: T09CM00362

Parcel: 11615088L

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00362

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/19/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/12/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
FRONT LOBBY OK
06/08/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. RELOCATE DUCT SMOKE DETECTOR TO ALLOW ACCESS AT ELEC. ROOM
2. COMPLETE DUCT SMOKE DETECTORS INSTALLATION
3. COMPLETE INSTALLATION OF INSULATION AT BRANCH TAPS
4. COMPLETE INSTALLATION OF ACCESS DOORS AND LABEL
5. FIRE/SMOKE/DAMPERS AT N.E. CORNER OF UNIT HAVE METERS IN WALL, CORRECT PRIOR TO NEXT INSPECTION
06/04/2009 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
03/25/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*