Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2009 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/19/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/12/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* FRONT LOBBY OK |
|
| 06/08/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. RELOCATE DUCT SMOKE DETECTOR TO ALLOW ACCESS AT ELEC. ROOM 2. COMPLETE DUCT SMOKE DETECTORS INSTALLATION 3. COMPLETE INSTALLATION OF INSULATION AT BRANCH TAPS 4. COMPLETE INSTALLATION OF ACCESS DOORS AND LABEL 5. FIRE/SMOKE/DAMPERS AT N.E. CORNER OF UNIT HAVE METERS IN WALL, CORRECT PRIOR TO NEXT INSPECTION |
|
| 06/04/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/25/2009 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |