Permit: T09CM00352

Parcel: 14026045A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00352

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/05/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/30/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TEMP POWER FOR TEST
SUBJECT TO POSTING OF BOND
04/29/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
INFORMED JERRY DUFFY JR. THAT THE ELECTRICAL DEPARTMENT CONCURRED THAT CONDUCTORS TO BE RUN ISOLATED TO MEET REQUIREMENTS OF 408.3 (A)(3)
04/20/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/20/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MEET JERRY DUFFY JR TO DISCUSS MANUFACTURES INSTALLED BARRIERS. TOOK PHOT TO DISCUSS WITH ELECTRICAL DEPT. FOR RULING.
WILL CONTACT JERRY WITHIN 24 HOURS
04/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
MEET CONTRACTOR - JERRY DUFFY JR -
TO DISCUSS SWITCH BOARD WIRING
CONTRACTOR TO FLEX OUT TO NEW SERVICES TO MEET REQUIREMENTS OF 408.3 CONTRACTOR TO CHECK SETTINGS OF ADJUSTABLE TRIP BREAKER FOR USE AT 200 AMPS.
ENGINEER TO NOTE CHANGE IN BREAKER OR FUSED DISCONNECT FOR SPACES WITH A LETTER.
04/09/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK HARD LID BATHROOM

STRAP M/C 12" OF EXH. FAN
04/06/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL ROOM #2
04/03/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/02/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROOMS BATHROOMS AND JANITOR
03/19/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK DEMISING WALLS
2. OK WALLS RMS. EXCEPT RMS. 2, 6 AND 7