Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T09CM00303
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2009 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/24/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/17/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSULATE CHILLER PIPING 2. PROVIDE ACCESS TO DISCONNECT 3. PROVIDE DOCUMENTATION OF PLENUM RATED CONDENSATE PUMP 4. ONLY NON-COMBUSTIBLE MATERIAL ALLOWED IN RETURN PLENUM |
|
| 03/11/2009 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/10/2009 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WORK PROGRESSING. 1. DISCUSSED SHEETROCK COVERING IN RETURN PLENUM 2. ACCESS TO FAN COILS MUST BE LARGE ENOUGH TO REMOVE THE LARGEST PIECE OF EQUIPMENT. |
|
| 03/06/2009 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMBUSTIBLE MATERIAL NOT ALLOWED IN A RETURN AIR PLENUM. ISOLATE THE PLENUM. NO PVC OR WOOD ALLOWED. CPVC OK. |