Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM00303
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* UNIT #13, 14, 15, 16 ALL OK WALLS AND CEILING |
|
| 03/10/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FIRE CAULK NOT FOR BOXES - USE APPROVED FIRESTOPPING METHODS 2. #8 & LARGER TO BE STRANDED IN RACEWAYS - 310.4 3. USE APPROVED ALUMINUM TO COPPER CONNECTIONS 4. GROUND ALL METAL BOXES 5. FINISH CONNECTION OF FLEX AND STRAPPING |
|
| 03/09/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* #15 & #13 1. PLEASE ADD BUILDING DESIGNATOR TO PERMIT 2. USE APPROVED LUG IN JUNCTION BOX 3. CLEAN SURFACE UNDER LUG 250.12 4. ONLY ONE CONDUCTOR PER TERMINAL LUG 5. GROUND METAL JUNCTION BOX 6. PREVENT SPREAD OF COMBUSTION 300.21 AT FIREWALL NO BACK TO BACK 7. SUPPORT NM CABLES ABOVE PANEL 8. PROTECT NM CABLE AT ENTRANCE TO CONDUIT |