Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T09CM00303

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/12/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
UNIT #13, 14, 15, 16 ALL OK
WALLS AND CEILING
03/10/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FIRE CAULK NOT FOR BOXES - USE APPROVED FIRESTOPPING METHODS
2. #8 & LARGER TO BE STRANDED IN RACEWAYS - 310.4
3. USE APPROVED ALUMINUM TO COPPER CONNECTIONS
4. GROUND ALL METAL BOXES
5. FINISH CONNECTION OF FLEX AND STRAPPING
03/09/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
#15 & #13
1. PLEASE ADD BUILDING DESIGNATOR TO PERMIT
2. USE APPROVED LUG IN JUNCTION BOX
3. CLEAN SURFACE UNDER LUG 250.12
4. ONLY ONE CONDUCTOR PER TERMINAL LUG
5. GROUND METAL JUNCTION BOX
6. PREVENT SPREAD OF COMBUSTION 300.21 AT FIREWALL
NO BACK TO BACK
7. SUPPORT NM CABLES ABOVE PANEL
8. PROTECT NM CABLE AT ENTRANCE TO CONDUIT