Permit: T09CM00283

Parcel: 14002010A

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
12/07/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) OK FOR TILES MECHANICAL ONLY
11/09/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SUPPLY FLEX CONNECTORS NEED TO BE SEALED
2) EXPOSE QUAD DAMPER HANDLES
3) WRAP CONDENSATE PIPING PER SPEC 210
09/01/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*