Permit: T09CM00281

Parcel: 12507400A


Addresses:

2500 E 6TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
08/12/2009 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
1) TERMINATE CONDENSATE INTO AN APPROVED LOCATION
2) PROVIDE A FRESH AIR INTAKE
3) SUPPORT RETURN DUCT ON ROOF
4) PROTECT LOW VOLTAGE WIRE
5) TURN SLEEPERS TO SPAN ROOF JOISTS-LEVEL UNIT
6) SUPPORT GAS LINE
7) RE-SEAL DUCT ON ROOF
08/11/2009 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ONE ON SITE, BLDG LOCKED