Permit: T09CM00276

Parcel: 13624446A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00276

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/20/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/18/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL LOCK NUT ON PVC CONNECTOR
2. GEC TO TERMINATE AT EQUIPMENT GROUND BAR AT TRAILER PANEL
3. SERVICE CONDUCTORS TO BE MARKED SUNLIGHT RESISTANT NO MARKINGS ON CONDUCTORS
4. PVC FROM EXPOSED TO BE SCHEDULE 80
5. PVC TO EXTEND MIN. 18" BELOW GRADE AND NEED BUSHED ADAPTORS WHERE CONDUCTORS ENTER PVC UNDERGROUND