Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T09CM00276
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/20/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/18/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL LOCK NUT ON PVC CONNECTOR 2. GEC TO TERMINATE AT EQUIPMENT GROUND BAR AT TRAILER PANEL 3. SERVICE CONDUCTORS TO BE MARKED SUNLIGHT RESISTANT NO MARKINGS ON CONDUCTORS 4. PVC FROM EXPOSED TO BE SCHEDULE 80 5. PVC TO EXTEND MIN. 18" BELOW GRADE AND NEED BUSHED ADAPTORS WHERE CONDUCTORS ENTER PVC UNDERGROUND |