Permit: T09CM00257

Parcel: 12710084B


Addresses:

6260 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T09CM00257

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2009 MECHANICAL - ABOVE CEILING Approved
03/30/2009 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. PROVIDE A SECURE SERVICE PLATFORM FOR FAN COIL.
2. PROVIDE 15A OVERCURRENT PROTECTION FOR FAN COIL.
3. PROVIDE A LIGHT AND RECEPTACLE IN ATTIC AT FAN COIL.
4. PROVIDE MIN. 1" CLEARANCE FROM COMBUSTIBLES WHERE OVER FLUE PENETRATES THE CEILING AND ROOF.
5. REMOVE THE FOIL TAPE FROM FLUE PIPING.