Permit: T09CM00249

Parcel: 13707045F


Addresses:

4975 S LIBERTY AV

Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
01/31/2011 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
01/13/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) OK 2ND FLOOR A/C DISCONNECT
01/11/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) WITNESSED FIELD INSPECTION FROM UL FOR LABELING OF SES-LABELING IS NOT CORRECT
01/10/2011 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) FINISH DISCONNECTING MEANS SMAL A/C
2) FINISH EXIT SIGN NORTH 2ND FLOOR
12/29/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
12/14/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) NOTE 408.5, 352.46 AND 300.4
2) NEED NTRL FIELD INSPECTION TO VERIFY VOLTAGE OF SWITCHBOARD LABELS STATE BOTH 208/120 AND 480/277
3) WILL NEED LETTER OF TORQUE
4) CONNECT MAIN BONDING JUMPER
5) NEED ADDRESS LABELING
6) WILL NEED BOND FOR TEMP POWER
11/12/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/27/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/25/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/19/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/15/2010 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
10/13/2010 ELECTRIC - PROGRESS Not ready for Inspection IVRS - Inspection :*
1) ANSWERED QUESTIONS
10/08/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/05/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/04/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) STRAP FIRE ALARM CABLING 770.24
2) PROTECT FIRE ALARM CABLES AT STUDS
3) MAINTAIN FIREWALL SEPERATION TO CORRIDOR BOXES
4) SECURE NM CABLE WITHIN 12" OF PANELS
09/30/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/28/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/27/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/24/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/23/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
09/15/2010 ELECTRIC - PROGRESS Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
08/06/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
08/02/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK 4 PVC AT TRANS PAD ONLY
S PACK APART FOR BILL ENDS
07/26/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
07/12/2010 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1) TEMP SERVICES TO BE PER TAP RULES 240 & SERVICES-230 FOR SEPERATE STRUCTURES
2) ANSWERED QUESTIONS