Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2009 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 08/19/2009 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE FAULT CURRENT FROM TEP XFMR PER NOTE ON PLANS 2) PROPERLY INSTALL LOCK NUTS 3) BOND SERVICE RISER PER NEC 250.92 AND 250.102 4) STRAP GROUNDING ELECTRODE CONDUCTOR TO BLDG |