Permit: T09CM00205

Parcel: 12216224B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/27/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/24/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CANNOT ENTER LB OTHER THAN THROUGH RACEWAY CONNECTION
2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL
3. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS
4. LABEL PANEL COVER AND CIRCUITS PER 408.4
5. SEAL UNUSED CONDUIT OPENINGS ABOVE PANEL
6. BOXES MORE THAN 1/4" -- 314.20
7. IF ATTACHING FIXTURES ON CORNERS USE 4 SCREWS
8. REVISE PLANS FOR LIGHTING CHANGES AND SERVICES AND PANELS
9. FINISH CROSSOVER OF PANELS
10. NEED TO VERIFY LIGHT/EXITS PER 700.12 (F)