Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/24/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. CANNOT ENTER LB OTHER THAN THROUGH RACEWAY CONNECTION 2. CLEAN EXCESS DIRT & FOREIGN MATERIAL FROM PANEL 3. GROUNDING ELECTRODE CONDUCTOR TO BE CONTINUOUS 4. LABEL PANEL COVER AND CIRCUITS PER 408.4 5. SEAL UNUSED CONDUIT OPENINGS ABOVE PANEL 6. BOXES MORE THAN 1/4" -- 314.20 7. IF ATTACHING FIXTURES ON CORNERS USE 4 SCREWS 8. REVISE PLANS FOR LIGHTING CHANGES AND SERVICES AND PANELS 9. FINISH CROSSOVER OF PANELS 10. NEED TO VERIFY LIGHT/EXITS PER 700.12 (F) |