Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T09CM00198
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2009 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/09/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. UNABLE TO LOCATE PLAN. I FOUND THE PLAN. 2. CONTINUED "NOT READY" MAY RESULT IN A REINSPECTION FEE 3. PLAN CALLS FOR CHROME PLATED SUPPLIES 4. PLAN CALLS FOR CHROME PLATED TRAP - THIS WOULD INCLUDE 5. BRANCH TAILPIECE AND SLIP NUTS 6. DID NOT LOCATE VERIFICATION OF STERILIZATION 7. DID NOT LOCATE CLEAN BACTERIA REPORT SEE NOTE #2 |
|
03/03/2009 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE SEE NOTES FROM 3/2/08 INSPECTION & COMPLY WITH ALL NOTES. YOUR HOSE BIB REQUIRES A VACUUM BREAKER. ALSO. |
|
03/02/2009 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE PLUMBING WORK, PROVIDE CHLORINE & BACTERIA REPORT FOR POTABLE WATER |