Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T09CM00191
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/17/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/12/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK 120 V ELECTRIC 2) PLEASE RECALL AFTER VDV CABELING IS DONE |