Permit: T09CM00190

Parcel: 122154490

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/12/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/07/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT MC CABLE UPON EXITING WALL
2. REMOVE OR SUPPORT CONDUIT ON GRID
3. SUPPORT VDV CABLING OR REMOVE 725.69
800.6 & 24, 300.11

$150.00 TO BE CHARGED TO BARKER MORRISSEY ACCOUNT FOR AFTER HRS. INSPECTION.