Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2009 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 03/11/2009 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SECONDARY GROUND ROD MINIMUM 6' APART 2) SECURE #4 TO BLDG 3) PROVIDE GAS & WATER BONDS 4) LABEL CIRCUITS |