Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/27/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUIT TO SHALLOW U.G MIN. DEPTH 18" PER 300.5 NEC USE SCH.80 ABOVE GROUND C.O.T CODE ADDENDUMS 2. CONTR. TO OPEN ALL J-BOXES INCL. GUTTER FOR INSPECTION |