Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T09CM00153
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) NOTE: ATTIC UNIT MINIMUM CIRCUIT AMPS 43.8/47.8, MAX OVER CURRENT 45/50 AND 30/30 FUSES INSTALLED, SHOULD BE 40/40 |
|
06/15/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HOOK UP ELECTRIC TO H20 HTR 2) NEED LADDER FOR ATTIC ACCESS |
|
06/12/2009 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |