Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2009 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/18/2009 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOX NOT ATTACHED TO STUD AT FRONT BEDROOM 2) FINISH POP OUTS AT FRONT 3) SUPPORT 4 GANG BOX AT BACK OF HOUSE AND BY FRONT DOOR 4) WIRE NUT GROUND WIRE TOGETHER AT OUTLETS 5) SUPPORT 3" DRAIN ABOVE HOUSE TO GARAGE MINIMUM 4' 6) BOND TO GAS LINE 7) WIRES AGAINST GUSSETS OF FLOOR TRUSSES ABOVE HOUSE TO GARAGE DOOR 8) DRAFT STOP TUBS AT 2ND FLOOR |