Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/20/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/12/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK ELECTRIC ABOVE CEILING |
|
| 06/10/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCES IN FRONT OF XFMR 2. CAP UNUSED CONDUIT OPENINGS ABOVE PANELS 3. BOXES OVERFILLED 4. MANUFACTURES CLIP FOR FIXTURES TO BE EFFECTIVE 5. PLEASE VERIFY TRANSFORMERS ARE RATED FOR AIR HANDLING CEILING |
|
| 05/11/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |