Permit: T09CM00141

Parcel: 11615088L

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/31/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/24/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) BOTH DSD TEST OK
2) PROVIDE SHELL FINAL PRIOR TO T.I. FINAL APPROVAL
07/20/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 1 OF 2 DUCT SMOKE DETECTORS FAILED TEST, (SOUTH) UNIT DID NOT SHUT DOWN
07/17/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) SMOKE TEST FAILED