Permit: T09CM00132

Parcel: 12913101C


Addresses:

900 E 31ST ST

Inspection Status: Partial Approval

Inspection History: FRAMING

Date Description Inspector Results Comments
02/12/2009 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING ALL TRADES
2) NOTE 2 FROM PREVIOUS
02/05/2009 FRAMING Not ready for Inspection IVRS - Inspection :*
1. NEED PRESS TREATED BOTTOM PLATES
2. NEED HARD WIRED, SMOKE DETECTORS
3. INSIDE (SUB-PANEL) WIRING, ISOLATE NEUTRALS GROUNDS, BOND AND GRD. BUSS 20 AMP. BREAKER FED WITH A WHITE WIRE, HOT WIRE NOT CONNECTED TO ANYTHING
4. GFCI PROTECTION KIT. COUNTER
5. NEED SWITCHED LIGHT FOR EA. BEDROOM
6. HEAT SOURCE REQ'S OWN CIRCUIT
7. CLEAN UP ALL BOXES WIRING INSIDE