Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 07/31/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" AT TILES 314.20 2) LABEL OUTSIDE COVERS 210.5 (C) 3) FINISH EQUIPMENT ROOMS ROOF: 1) BOND BUSHINGS 250.97 2) MAINTAIN WORKING CLEARANCES 3) BOND A/C DISCONNECT AND LABEL |
|
| 06/29/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) ABOVE 24" AT PARKING TO BE PER 300.5 OR ENCASED 2) OK POLE TO POLE TO BLDG EXCEPT AS NOTED 3) OK WALLS ? ROOM EXCEPT SOUTH WALL |
|
| 06/19/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 3-3" PVC CONTINUATION TO TRANSFORMER AND OK ROOM 126 WALLS |
|
| 04/29/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 04/28/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3 - 3" PVC FEEDER TO SES |
|
| 04/16/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK DATA RUNS UNDER X-RAY |
|
| 04/09/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SMALL MRI DATA RUNS |
|
| 04/08/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 3 FLOOR BOXES OK DATA FOR BIG MRI ROOM |
|
| 04/02/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK 1 - 4" AND 1 - 2 1/2" PVC PRIMARY CONDUITS |
|
| 03/31/2009 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PVC CONDUITS UNDER SLAB NON-PATIENT CARE AREAS |