Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/27/2009 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 03/13/2009 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1. REVISED PLANS NEED TO GO THROUGH PLAN REVIEW. WILL NEED DISCONNECTING MEANS FOR NEW XFMR FOR A STRUCTURE BASED ON 225.31, 225.32 2. OK U.G. TO PROPOSED XFMR LOCATION 3. OK U.G @ 480V SERVICE LOCATION NORTH SIDE OF PARK 4. GROUND RODS TO BE MIN. 6' APART @ 480V SERVICE |