Permit: T09CM00102

Parcel: 13101002L


Addresses:

2400 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T09CM00102

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2009 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
03/13/2009 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1. REVISED PLANS NEED TO GO THROUGH PLAN REVIEW. WILL NEED DISCONNECTING MEANS FOR NEW XFMR FOR A STRUCTURE BASED ON 225.31, 225.32
2. OK U.G. TO PROPOSED XFMR LOCATION
3. OK U.G @ 480V SERVICE LOCATION NORTH SIDE OF PARK
4. GROUND RODS TO BE MIN. 6' APART @ 480V SERVICE