Permit: T09CM00100

Parcel: 132171280

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/05/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/04/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL BONDING SCREW IN DISCONNECT FOR CONDENSING UNIT
2. PLAN CALLS FOR #10's TO BE INSTALLED TO CONDENSING UNIT
3. HAVE 2 POLE 50 ON #12's TO FAN COIL UNIT PLEASE VERIFY PROPER SIZE WITH ENGINEER
4. PLAN CALLS FOR 2 AMP FUSES FOR FAN COIL UNIT
5. WHITE WIRES NOT TO BE INSTALLED IN RACEWAY AS PHASE CONDUCTORS. PHASE CONDUCTORS TO BE IDENTIFIED ALONG ENTIRE LENGTH IN RACEWAY
6. PATCH AROUND SWITCH BOXES NO MORE THAN 1/8" GAP
7. NEED SERVICE RECEPT. FOR CONDENSING UNIT TO BE WITHIN 25' AND GFI PROTECTED
02/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ANSWER AT DOOR
RECALL INSPECTION