Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T09CM00096
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/21/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
04/21/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/27/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
02/02/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLAN CALLS FOR LOW VOLTAGE RACEWAYS TO BE 1" 2. PLAN CALLS FOR NEW PANEL TO BE 42 CIRCUIT WITH 1 1/2" RACEWAY WITH #2 AWG 3. PLAN CALLS FOR ALL CIRCUITS IN SPACE TO ORIGINATE IN NEW PANEL 4. PLAN DOES NOT ALLOW FOR MORE THAN 4 CURRENT CARRYING CONDUCTORS IN RACEWAY 5. LOW VOLTAGE CABLES TO BE PROTECTED WHEN RUN THROUGH METAL STUDS |