Permit: T09CM00071

Parcel: 122173110

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T09CM00071

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/05/2010 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/19/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WRONG PERMIT
02/13/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK UNITS E & H
02/11/2009 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLANS CALL FOR BATH GFCI TO BE 20 AMP. CIRCUIT
NOW ON 15 AMP. BEDROOM BATH CIRCUIT - 210.8, 210.52
02/09/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
02/03/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
E:
1. INSTALL ALL PLATES
2. BOXES TO BE FLUSH AT COMBUSTIBLES
3. INSTALL EXHAUST FAN
4. PANEL DIRECTORY TO BE AS PER 408.4

H:
1. BOXES TO BE FLUSH AT COMBUSTIBLES
2. GROUNDED RECEPTACLES ON UNGROUNDED CIRCUITS
3. WHERE IS JUNCTION BOX FOR WIRING OF FEEDER
4. PANEL DIRECTORY TO BE AS PER 408.4
5. A CONNECTOR IS NEEDED AT HOOD
6. SERVICE IS AN UNGROUNDED SYSTEM - CORRECTLY IDENTIFY GROUNDED CONDUCTOR AND PROVIDE A GROUNDING EQUIPMENT CONDUCTOR TO NEW PANEL
7. PROVIDE ARC FAULT AS PER 210.12
8. PLEASE VERIFY BOXES ARE FAN RATED
02/02/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED -- NO ACCESS
01/28/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. LIVING ROOM OUTLETS, BEDROOM, REFRIGERATOR ARE LOOSE AND DON'T WORK
2. LIGHT FOR STOVE HOOD DOESN'T WORK
3. NEED SMOKE DETECTORS FOR UNIT H ONLY