Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2010 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
| 04/20/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE LETTER FROM ENGINEER GIVING OK FOR THREADED BLK IRON PIPE ON 5 PSI PIPING SYSTEM IN PLACE OF SPEC. SOCKET WELD FITTINGS 2) REVISE AND GET APPROVED PAGE P-211 FOR REFRIGERANT DETECTION SWB-1, ACID WASTE NOT INSTALLED DUE TO CONDENSING BOILER BY SEPERATE CONTRACTOR 3) REMOVE AND CAP OLD GAS PIPING NOT IN USE 4) CORRECT LEAK ON AC-6 5) FAILURE TO COMPLY WILL RESULT IN REFEE |
|
| 04/19/2010 | PLUMBING - GAS PRESS TEST FNL | Partial Approval | IVRS - Inspection :* 1) REPAIR LEAK AT COUPLING ON ACV-6 VALVE IS OFF |
|
| 04/16/2010 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE MINIMUM SOAP TEST ON REGULATORS AND ASSOC. PIPING |