Permit: T09CM00062

Parcel: 13414011A


Addresses:

401 S PRUDENCE RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Date Description Inspector Results Comments
05/04/2010 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
04/20/2010 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE LETTER FROM ENGINEER GIVING OK FOR THREADED BLK IRON PIPE ON 5 PSI PIPING SYSTEM IN PLACE OF SPEC. SOCKET WELD FITTINGS
2) REVISE AND GET APPROVED PAGE P-211 FOR REFRIGERANT DETECTION SWB-1, ACID WASTE NOT INSTALLED DUE TO CONDENSING BOILER BY SEPERATE CONTRACTOR
3) REMOVE AND CAP OLD GAS PIPING NOT IN USE
4) CORRECT LEAK ON AC-6
5) FAILURE TO COMPLY WILL RESULT IN REFEE
04/19/2010 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
1) REPAIR LEAK AT COUPLING ON ACV-6 VALVE IS OFF
04/16/2010 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE MINIMUM SOAP TEST ON REGULATORS AND ASSOC. PIPING