Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2010 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) UNDERGROUND AND PIPE WRAPS RESTROOM 104 OK |
|
| 02/22/2010 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST 3" DRAIN FROM HALLWAY 116 THRU TO RESTROOM 117 PARTIAL, PROVIDE LONG RADIUS DRAINING FITTINGS FOR HORZONTAR VENTS FLOOD RIM OF FIXTURES WILL ALLOW RUN TEST ON THIS 2" LAV DRAIN RESTROOM IN 117 OK, UNDERGROUND ONLY. |
|
| 12/18/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND CONTINUATION FOR EWC ROOM 130 AND BATHROOM 117 WATER TEST DWV OK FOR INITIAL P221 |
|
| 12/07/2009 | PLUMBING - ROUGH, SOIL | Partial Approval | 1) DWV AT DF WITH TEST OK 2) PROVIDE CONTINOUS FOAM PIPE WRAP FOR ALL PIPING IN MASONRY 3) HBS NOT PER SPEC. L W WITH TEST AND SLEEVE OK |
|