Permit: T09CM00046

Parcel: 115080080


Addresses:

1300 N STONE AV

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
01/25/2011 FIRE - FINAL Approved
09/22/2010 FIRE - FINAL Not ready for Inspection Not ready forn inspection 9/22/10
03/30/2010 FIRE - FINAL Denied Not approved 3/30/10
1.) Need addtress numbers for the building. Numbers must be readily visible, must contrast with background. Numbers must be 12 inches tall minimum. Must relocate numbers to the main driveway area.
2.) Need panic hardware on doors leading out of the banquet room. x7
3.) Need illuminated exit sings over:
a.) N exit door, lounge area
b.) over main lobby exit door
4.) Need emergency back-up lighting for same doors.
5.) Need access to closets in banquet areas.
6.) Must maintain a clear and unobstructed path to all exit doors at all times.