Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/28/2009 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/26/2009 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SEISMIC WIRES SUPPORTING BOXES & MC NEEDS TO BE TIED OFF BOTH ENDS 300 NEC. |