Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2010 | FIRE SPKLR - FINAL | Approved | ||
| 12/31/2009 | FIRE SPKLR - FINAL | Partial Approval | TEMP C OF O APP. 1. NEED TO PAINT PIPING TO PORTE CORCHET 2. INSTALL SPRINKLER COVERAGE BOTTOM OF ELEVATOR SHAFT. |
|
| 12/28/2009 | FIRE SPKLR - FINAL | Not ready for Inspection | 1. NEED TO INSPECT ALL V-TECHS ON 3RD FLOOR WAS ABLE TO OPEN TO LOOK INSIDE 2. FIX LEAKING AND PAINTED HEADS IN THE FOLLOWING AREAS; ROOMS 303-307-3110313-315-317-324-321-323-324-326-325-330-333 3. ADD HEAD BOTTOM OF ELEVATOR SHAFT. 4. ATTIC SPRINKLERS SHALL BE FROM 4' TO 6' APART FROM EACH OTHER CORRECT TWO SPRINKLERS ON THE SOUTH END. |