Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2009 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
| 12/17/2009 | FIRE SPKLR - OH PIPING & HYDRO | Not ready for Inspection | 150 PSI test ok 1. Master bedroom #1 heads to far off wall 8'-4". 2. Add a head in the old mech room that was chaged into a pots and pans storage room. 3. Need as builts showing changes. 4. If adding a backflow on 1" line then we will need new calculations. |