Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU01709
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2010 | FIRE - ALARM FINAL | Approved | 24 STAND-BY TEST PASSED RUN TIME FOR 7 MINUTES | |
10/18/2010 | FIRE - ALARM FINAL | Partial Approval | SHUT ALL 120V POWER OFF TO THE ALARM SYSTEM FOR 24 HOUR BATTERY STAND-BY TEST - STARTED AT 0930 HOURS FIXED ANNUNCIATOR PANEL BY MAKING CHANGES TO THE PROGRAMING |
|
10/13/2010 | FIRE - ALARM FINAL | Partial Approval | 5TH FLOOR PASSED - PHONE LINES PASSED STILL NEED TO DO 24 HOUR STAND BY TEST |
|
10/12/2010 | FIRE - ALARM FINAL | Denied | 1. ANNUNCIATOR PANEL FAILED WHEN SUN HITS ITS SCREEN IS ALL BLACK 2. 5TH FLOOR STROBES FAILED ON EASTSIDE OF BUILDING 3. PHONES LINES FAILED TO WORK - NEED TO TEST 4. NEED TO DO 24 HOUR STANDBY TEST ON BATTERIES |