Permit: T09BU01702

Parcel: 115044540


Addresses:

1135 N PARK AV


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T09BU01702

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/21/2009 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/10/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE HINGE KIT
12/08/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHOWED UP ON SITE AT 10:35 AM EMPLOYEE INSIDE BLDG AND DENIED ACCESS, SAID THE OWNER WOULD BE HERE TOMORROW-REFEE HAS BEEN ATTACHED
11/24/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE HOOD IS OK FOR TYPE I, HOWEVER THERE ARE A FEW HOLES IN THE HOOD THAT NEED TO BE SEALED
2) YOU CAN USE NUTS, BOLTS AND WASHERS IN HOLES
3) PROVIDE A GREASE RECEPTOR ATTACHED TO THE FAN, DO NOT USE A PLASTIC BUCKET
4) INTERLOCK THE MAKE UP AIR WITH EXHAUST FAN
5) GREASE DUCT NEEDS TO BE WELDED TO THE METAL PLATE AT TERMINATION
6) PROVIDE A HINGE KIT ON FAN AND A GASKET UNDER THE FAN
11/19/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSPECTIONS ARE DONE BETWEEN 8:00 AM AND 3:30 PM MONDAY THRU FRIDAY, I WILL NOT DO INSPECTIONS ON A HOT HOOD, INSPECTION NEEDS TO BE DONE ON HOOD PRIOR TO KITCHEN START UP IN AM. ANYMORE DENIED INSPECTIONS WILL REQUIRE REFEE ATTACHED
11/17/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNABLE TO GAIN ACCESS, PROVIDE LADDER FOR ROOF ACCESS
2) LET EMPLOYEES INSIDE KNOW THAT INSPECTOR IS COMING