Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2010 | FIRE - ALARM FINAL | Approved | Approved 6/29/10 | |
| 05/20/2010 | FIRE - ALARM FINAL | Denied | 1. RELABEL PLANS FOR PROPER FLOORING 2. NEED AS BUILTS FOR PROPER FLOOR PLAN 2ND LEVEL, NO HALLWAY JUST ONE OPEN BUSSINESS. WLL NEED TO TEST THIS AREA. PG. FA5 3. NEED TO CHECK SPACING IN HALLWAY 46' NO MORE THAN 42' ALLOWED. PG. FA5 |