Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T09BU01668
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/29/2010 | FIRE - ALARM FINAL | Approved | Approved 6/29/10 | |
05/20/2010 | FIRE - ALARM FINAL | Denied | 1. RELABEL PLANS FOR PROPER FLOORING 2. NEED AS BUILTS FOR PROPER FLOOR PLAN 2ND LEVEL, NO HALLWAY JUST ONE OPEN BUSSINESS. WLL NEED TO TEST THIS AREA. PG. FA5 3. NEED TO CHECK SPACING IN HALLWAY 46' NO MORE THAN 42' ALLOWED. PG. FA5 |